HDC-30G1

HDC-30G1

HDC-30G1 Generator

Specifications

Prime Power Standby Power Engine Type
30KVA 33KVA Diesel, 4-Stroke, Water-Cooled
Fuel tank Capacity Engine Filtration System
155 Liters Dry air filter fuel filter lube oil filter
Cooling Radiator Exhaust System
Radiator and cooling fan complete with safety guard design to cool the engine on high ambient temp. Heavy duty industrial type exhaust silencer Mechanically welded chassis with vibration isolator24V charged DC starting battery with electrolyte & cables
METERING & ALARM INDICATION
Generator frequency Under speed, over speed generator Volt Generator current Engine oil pressure Fuel

Alternator

Model Type Voltage Power Factor Insulation Class Excitation System
Leroy Somer LSAA2.2L9 Synchronous 400V, 3-Phase, 50Hz 0.8 H Brushless / Automatic Voltage Regulator (AVR)

Alternator Additional Information

Insulation Class Winding Pitch Excitation System Terminals
H 2/3 (bob 6) SHUNT, A R E P or PMG Drip proof IP 23
AVR Model Short Circuit Current Altitude Overspeed
MX321, MX341 300% (3 IN) : 10s ≤ 1000 m 2250 min-1
Air Flow THD No Load THD Linear Load Waveform
0.27 m³/s (50Hz) / 0.32 (60Hz) < 2% according to IEC < 3% according to IEC NEMA = TIF (**): < 50

Engine

Brand Model
Cummins 4BT3.9-G1

Engine Technical Data

Cylinders Arrangement Cycle Induction System
4 In-line Four stroke Natural Aspirated
Compression Ratio Bore Stroke Capacity
17.3 : 1 102 mm 120 mm 3.9 litres
Rotation Firing Order
Clockwise view from front 1, 2, 3

Exhaust System

Maximum Back Pressure Exhaust Outlet Size
10 kPa 75 mm
Meets Tier 2 or Tier 3 EPA emissions standards, Designed to comply with ISO8528/GB2820.

Sound Pressure Level

At-1500 rev/min At-1800 rev/min
75dBA 85dBA
Overall sound pressure level (cooling pack and air cleaner fitted)
Top